From basic DOL starters to fully automated batching plant control systems — we design, fabricate, wire, and test the complete range of industrial control panels.
| Rated Current | Up to 3200A |
| Voltage | 415V ±10%, 3-phase, 4-wire |
| Frequency | 50 Hz ±5% |
| Short Circuit Rating | Up to 50kA (with bus coupler) |
| Protection Class | IP54 standard, IP65/IP66 optional |
| Enclosure | CRCA MS powder-coated / SS304 |
| Busbar | Copper / Aluminium, shrouded |
| Components | Schneider, ABB, Siemens, L&T |
| PLC Brands | Siemens, Allen-Bradley, Mitsubishi, Delta |
| HMI | 7" / 10" touch panel (client's choice) |
| Communication | Modbus RTU/TCP, Profibus, EtherNet/IP |
| I/O Modules | DI, DO, AI (4–20mA), AO, RTD |
| Power Supply | 24V DC SMPS (redundant optional) |
| Protection | IP54, IP65, or IP66 as required |
| Programming | Ladder, FBD, ST, SFC (IEC 61131) |
| Documentation | GA, SLD, I/O list, ladder program PDF |
| Voltage | 415V, 3-phase, 50Hz |
| kVAr Range | 10 kVAr to 500 kVAr (steps of 10–50 kVAr) |
| Target PF | Adjustable 0.90 to 0.99 (typically 0.97+) |
| Stages | 4 to 12 steps per panel |
| Capacitors | ICAR / Epcos, self-healing film type |
| PF Relay | EPCOS BR6000 / Circutor MC5 or equivalent |
| Enclosure | MS powder-coated, IP54 minimum |
| ROI | Typically 12–24 months on penalty savings |
| Protection | Overload relay, short circuit breaker |
| Indications | Run (Green), Trip (Red), Power (Amber) |
| Control Supply | 230V AC from control transformer |
| Remote Provision | Remote start/stop terminals as standard |
| Ammeter | DIN rail type with CT |
| Wiring | FR, colour-coded PVC insulated cables |
| Ferruling | All wires numbered as per SLD |
| Testing | No-load run test before dispatch |
The most demanding environment in infrastructure: dusty, wet, continuous operation, 24×7 pressure to produce concrete on time. Our batching automation panels are engineered specifically for this challenge.